Class 105 Paper-Covered Film-Insulated Round Aluminum Magnet Wire

Thermal Class:105

Insulation materials:rope paper, kraft paper, or both

Insulation thickness:Single; heavy; triple; quad

Class 105 Paper-Covered Film-Insulated Round Aluminum Magnet Wire

Paper-Covered Film-Insulated Round Aluminum Magnet Wire is a type of wire commonly used in electrical applications, especially in motors, transformers, and other electromagnetic devices.

Insulating Material:

The insulating material shall be rope paper, kraft paper, or both. The paper covering shall be one or more tape layers wrapped firmly, closely, evenly, and continuously around the wire.

Thermal Class: 105 impregnated or in oil. The thermal class of fibrous-covered or paper tape–wrapped wire shall be based on experience.

The end point chosen for purposes of this publication is 20,000 hours. This means that the graph of the test data obtained when following the test procedure given in ASTM D 2307 must show an extrapolated life for the wire of 20,000 hours or more at or above the thermal class rating.

Insulation thicknessDiameter
single8-24 AWG min: 0.025mm-0.043mmmax: 0.551mm-3.338mm
heavy8-24AWGmin: 0.048mm-0.089mmmax: 0.577mm-3.383mm
triple14-24AWGmin: 0.074mm-0.122mmmax: 0.599mm-1.773mm
quad10-24AWGmin: 0.097mm-0.172mmmax: 0.635mm-2.789mm

See wire having two or three layers (N) and tape thickness of 0.051-0.076 mm.

Fibrous coverings shall be wrapped firmly, closely, evenly, and continuously around the wire. When more than one tape covering is applied, adjacent tapes shall be permitted to be wound in the same or in opposite directions. The relation of the percentage of overlap of the tape to the number of layers of tape is shown as follows:

Wrap DescriptionNumber of Tape Layers (N)
Percentage of Overlap
0n
Greater than 0 to 251.33n
Greater than 25 to 331.5n
Greater than 33 to 401.67n
Greater than 40 to 502n
Greater than 50 to 673n
Greater than 67 to 754n

Adherence And Flexibility: No openings sufficient to expose the bare or film-insulated conductor when wound on the following mandrel:

AWG SizeMandrel Size
8-13.55d
14-22.54d
23-243d

No openings sufficient to expose film-coated wire after elongation as follows:

AWG SizeElongation Method
8-13.515% (+2, -0)
14-22.510% (+2, -0)
23-248% (+2, -0)

Elongation: Not less than 10%

Feature of this type round aluminum magnet wire: Temperature Rating, Insulation Options, Conductor Material, Round Shape, Electrical Properties.

Versatile Applications: Class 105 Paper-Covered Film-Insulated Round Aluminum Wire finds applications in a wide range of electrical devices and systems, including motors, transformers, generators, and other electromagnetic devices where reliable and efficient electrical conduction is essential.